Model Number: 6-112

Kit Components: 20KV Volt LiteWire & Accessories, Insulated Electrode, Amp LiteWire & Accessories, Fluke 43, Hard Carrying Case

Amp Sensor Opening: 1.89 in. (4.8cm)

(Note: 30 and 40 kV systems with operating voltages of 10kV are available. Consult Fluke 43 Power Quality Analyzer Data Sheet for its specific specifications.)

Voltage (Using LiteWire)
Range: 1kV to 20kV
Basic Accuracy: +/- 2%
Frequency Range (Fundamental): 60 Hz or 50 Hz Models Available

Current (Using Amp LiteWire)
Range: 1 to 2000 Amps
Accuracy: +/- 2%
Frequency Range (Fundamental): 6 Hz - 65 Hz (Useable to 99.9 Hz)

Watts (Using Amp LiteWire)
Range: 0.0kW - 40MW or 0.0kVA - 40MVA
Accuracy: +/- 2%
Frequency Range (Fundamental): 6 Hz - 65 Hz (Useable to 99.9 Hz)

Harmonics
Voltage Accuracy: +/- 2% (6 Hz - 65 Hz)
Current Accuracy: +/- 3% (6 Hz - 65 Hz)
Current Maximum Harmonic: 51st (odd & even on screen)
Frequency Measurement Range: 6.0 Hz - 99.9 Hz (Fundamental)
Frequency Measurement Accuracy: +/- 0.3Hz

Mechanical
Operating Temperature: -22 to + 140 degrees F (-30 to +60 degrees C)
Housing: Shock & water resistant molded urethane
Hotstick mounting: Universal chuck adapter (Hotstick not included)
LiteWire Batteries: 9 volt alkaline