Model Number 950 Overhead Transformer Meter

Type Single phase, pole top transformer meter

Range of Operation
     Voltage 100 - 277 VAC
     Current 1 - 700 Amps

Resolution

Voltage 0.1 V

Current 0.1 A

Watts 0.1 kW

KWH 0.1 KWH

Accuracy

Current 1 A to 3 A 0.5% ± 2 digit

Current 3 A to 700 A 0.5% ± 1 digit

Voltage 0.5% ± 1 digit

KWH 1% ± 1 digit

Radio

Type & Band ISM 2.4 GHz

Transmit Distance 300 Feet (100 meters)

Transmit Power 63 mW (18 dBm)

Transmit Power (EU & Japan) 10 mW (10dB)

Mechanical

Weight 1.5 lbs (0.68 kg)

Sensor Opening 1 inch (25 mm)

Conductor Range 1/0 to 600 kcmil

Max Insulation Thickness Up to 100 mils (2.5 mm)

Power

System Line Powered

Clock Battery Backup 14 days

Battery 2 each CR2032 Lithium coin cells

Logging Capacity 330 days @ 5 min intervals

Software Requirements Windows XP (SP3), VISTA, Windows 7, & Windows 8