Live-Line Power Quality Meter
Model 8-084 Plus Live-Line Power Quality Meter
Range of Operation
True RMS Amps: 5 - 2000 A
Power Factor: 0.01 - (Lag) to 0.01 + (Lead)
THD Amps: 1 - 100%
Voltage: Rated 500 kV
Frequency: 60 Hz (57 to 63 Hz) or 50 Hz (47 to 53 Hz) Models available
Resolution
Amps 1.0 - 99A: 0.1 A
Amps 100 - 2000A: 1 A
Power Factor: 1.0 to 0.01
THD Amps: 1%
Accuracy
Amps: ± 1% ±2 Counts
Power Factor: ± .01 from .71 Lead to .71 Lag
THD Amps: ± 1% from 0 to 25% ±
Note: Accuracy is diminished if the current is less than 15 amps
Mechanical
Measurements: Stores Nine Readings
Wide Sensor Opening: 3.86 in, 9.8 cm
Wide Sensor Weight: 3.5 lbs, 1.58 kg
Operating Temperature: -22 to +140 degrees F (-30 to +6- degrees C)
Display: Graphics LCD
Housing: Shock & water resistant molded urethane
Controls: Single button operation
Hot stick mounting: Universal chuck adapter (Hot stick not included)
Battery: 9 volt alkaline
EEC Standards: Successfully passed international test standards indicated by CE